1515 Walbridge St
Red Bluff, CA 96080
06/02/2022 3:30 pm

3
Minor concern
13
Moderate concern
12
Major concern

How to read this report:

The defects within the report are organized into three categories. They are Minor Concern (in blue), Moderate Concern (in orange), and Major Concern (in red). The category that each defect is in does not determine the importance of the recommended repair. All defects noted on this report should be addressed. Health and safety concerns will be in the Moderate Concern or Major Concern, depending on how the perceived danger but these should be addressed ASAP. All repairs should be performed by licensed and/or qualified contractors in order to ensure the repairs are done safely and properly.

Minor Concern: Items or components of the home that are defective and, in the opinion of the inspector, may be considered general maintenance or are typical for the age of the home. Any recommended improvements to the home may also be in this category.

Moderate Concern: Items or components that were found to be defective and, if not addressed, these could lead to further problems. These defects are not considered to be routine maintenance. This category may also contain safety hazards or concerns.
Major Concern: Items or components that were defective and may require major/costly repairs.  This category may also contain serious safety hazards or concerns that are in need of immediate attention.

These categories are based on the inspectors professional judgement and are based on the conditions at the time of the inspection. This categorization should not be construed as to mean that items designated as a Minor Concern or Moderate Concern do not need need repaired or addressed. The recommendation in each comment is more important than the category in which the defect was placed in.


Limitations: In the event that the inspector was not able to inspect/test certain areas or components of the home, there may be a Limitations tab in that section of the report. The Limitations tab may show things that need to be further evaluated after the inspection. I recommend reading any Limitations in the report and addressing them as necessary. 


Photographs: Several photos and videos are in your inspection report. These photos are for informational purposes and may not include every instance or occurrence of a defect. For example, if the report has three photos of hail damage on the roof, this does not mean that there is only hail damage in those areas.


1 - Inspection Details

Type of Inspection
Pre-Purchase
Style of Home
Contemporary
In Attendance
Tenant
Occupancy
Furnished, Occupied
Utilities
Water, Gas, Electric
Weather
Clear
Occupied/Furnished Disclaimer

During the inspection, the home was furnished, staged, occupied, or had the current occupants belongings present. This limited the inspectors visibility and access to areas of the home, therefore not all receptacles, windows, wall surfaces, floor surfaces, countertop areas, etc. were tested or inspected. 

2 - For Your Information

Orientation: Pictures of the Exterior

The following pictures are of the exterior walls and are intended to help the person reading this report orient themselves with the home or to reference while reading the report. For example, if the Inspector states that there was a defect with a window on the West exterior, this section can be used to view a picture of the West exterior wall. 

Orientation: North Exterior
Orientation: South Exterior
Orientation: East Exterior
Orientation: West Exterior
Electrical - Main Disconnect: Location
On the South Exterior

I recommend that everyone living in the home familiarizes themselves with the location of the electrical service panel and the disconnect used to shut off power to the whole house. Knowing the location of the panel may be beneficial to all members of the family, whether it's to reset a tripped breaker or to disconnect power in the event of an emergency.

Gas - Main Shut Off Valve: Location
Against the West Exterior Wall

I recommend that everyone living in the home familiarizes themselves with the location of the main shut off valve for the gas. If home renovations are being done, it may be necessary to locate and turn off the gas. In the event that natural gas was smelled in the home, I recommend contacting the local utility company and evacuating the home until they evaluate the smell.

Water - Main Shut Off Valve: Location
Unknown

I recommend that everyone living in the home familiarizes themselves with the location of the main shut off valve for the water. In the event of a plumbing emergency, knowing where it is and how to turn the water off can limit damage and save time, money and avoid costly repairs from water damage.

$
Credit
Comment
2.4.1 - Water - Main Shut Off Valve

Main Water Shut-Off Valve - Unable to Locate

The main water shut off valve was not visible during the inspection. I recommend asking the sellers about it’s location. If they don’t know where it is then I recommend having it located or having one installed. 

Plumbing Contractor

3 - Roof Coverings & Drainage

General: Descriptions:

The materials, styles and components present and observable are described as follows:

General: Inspection Method
Ladder, Ground
General: Roof Type / Style
Gable
Coverings: Pictures of the Roof
Coverings: Material
3 Tab Shingles

I. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. the downspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure of the roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roof leaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectors opinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I. perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-covering material.

$
Credit
Comment
3.2.1 - Coverings

Poor Condition

The roof is in overall poor condition. I recommend having the roof evaluated and repaired/replaced as necessary by a qualified and licensed roofing contractor. 

Roofing Professional
$
Credit
Comment
3.4.1 - Gutters

No Gutters

There are no gutters installed. In order to prevent water near the foundation, which can cause structural/foundation damage, I recommend having gutters installed. 

Gutter Contractor

4 - Exterior

Descriptions:

The materials, styles and components present and observable are described as follows:

Inspection Method
Ladder, Ground

I. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C. adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconies and carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number of windows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adversely affect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-covering materials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediate balusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readily accessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H. inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind or geothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systems or cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrity of multiple-pane window glazing or thermal window seals.

$
Credit
Comment
4.1.1 - Stucco

Stucco - Cracking

Cracking was observed in areas of the stucco. In order to prevent moisture intrusion, I recommend having the stucco cracks repaired/sealed. 

Stucco Repair Contractor
$
Credit
Comment
4.2.1 - Exterior Doors

Damaged
Back Door

The exterior door(s) was damaged. I recommend having the door evaluated and repaired/replaced as necessary. 

Door Repair and Installation Contractor
$
Credit
Comment
4.3.1 - Windows

Window - Outer Sill Rot/Damage

The window(s) has some wood rot and damage on the outer window sill. I recommend having this evaluated and repaired/replaced as necessary. 

Window Repair and Installation Contractor
$
Credit
Comment
4.4.1 - Sidewalks, Patios, Porches, & Driveways

Guardrails/Handrails - Loose
Front Porch

Areas of the guardrails/handrails are loose. In order to increase the overall safety of the home and to prevent accidents/injuries, I recommend having this evaluated and repaired as necessary. 

Qualified Professional
$
Credit
Comment
4.4.2 - Sidewalks, Patios, Porches, & Driveways

Handrails - Missing

The front ramp is in need of handrails. It is recommended to have proper handrails installed in order to prevent accidents/injuries, particularly to the elderly. I recommend having handrails installed on all steps/stairs/ramps to prevent injuries. 

Qualified Professional
$
Credit
Comment
4.4.3 - Sidewalks, Patios, Porches, & Driveways

Ramp - Deteriorated

Areas of the ramp are soft and deteriorated, which could cause accidents/falls if it fails. I recommend this be repaired. 

Qualified Professional
$
Credit
Comment
4.5.1 - Soffits & Fascia

Soffit/Fascia - In Need of Repair
South Exterior

Areas of the soffit/fascia appeared to be in need of repair. I recommend having it evaluated and repaired as necessary. 

Siding Contractor

5 - Doors, Windows & Interior

Descriptions:

The materials, styles and components present and observable are described as follows:

Windows: Material
Aluminum
Floors: Interior Flooring
Some Areas Inaccessible

Not all areas of the home’s interior could be inspected due to the tenant occupying some areas with several large dogs. 

I. The inspector shall inspect: A. a representative number of doors and windows by opening and closing them; B. floors, walls and ceilings; C. stairs, steps, landings, stairways and ramps; D. railings, guards and handrails; and E. garage vehicle doors and the operation of garage vehicle door openers, using normal operating controls. II. The inspector shall describe: A. a garage vehicle door as manually-operated or installed with a garage door opener. III. The inspector shall report as in need of correction: A. improper spacing between intermediate balusters, spindles and rails for steps, stairways, guards and railings; B. photo-electric safety sensors that did not operate properly; and C. any window that was obviously fogged or displayed other evidence of broken seals. IV. The inspector is not required to: A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect floor coverings or carpeting. C. inspect central vacuum systems. D. inspect for safety glazing. E. inspect security systems or components. F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures. G. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. H. move suspended-ceiling tiles. I. inspect or move any household appliances. J. inspect or operate equipment housed in the garage, except as otherwise noted. K. verify or certify the proper operation of any pressure-activated auto-reverse or related safety feature of a garage door. L. operate or evaluate any security bar release and opening mechanisms, whether interior or exterior, including their compliance with local, state or federal standards. M. operate any system, appliance or component that requires the use of special keys, codes, combinations or devices. N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights. O. inspect microwave ovens or test leakage from microwave ovens. P. operate or examine any sauna, steamgenerating equipment, kiln, toaster, ice maker, coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other small, ancillary appliances or devices. Q. inspect elevators. R. inspect remote controls. S. inspect appliances. T. inspect items not permanently installed. U. discover firewall compromises. V. inspect pools, spas or fountains. W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects. X. determine the structural integrity or leakage of pools or spas.

$
Credit
Comment
5.2.1 - Windows

Window - Missing

There is a window that is missing. In order to prevent pest intrusion, moisture intrusion/damage and to increase security, I recommend a window be installed. 

Qualified Professional
$
Credit
Comment
5.3.1 - Floors

Flooring - Damage

Areas of the flooring have damage/imperfections present. I recommend having the flooring evaluated and addressed as necessary by a qualified contractor prior to closing. 

Flooring Contractor
$
Credit
Comment
5.4.1 - Walls

Drywall - Multiple Repairs Needed

Throughout the home, multiple areas of the interior walls appeared to be in need of drywall repair. I recommend having the home evaluated by a drywall contractor in order to have the damaged or missing drywall areas properly repaired.

Drywall Contractor
$
Credit
Comment
5.6.1 - Countertops & Cabinets

Cabinets - Pest Intrusion

An insect (cockroach) infestation was observed in most of the accessible cabinets during the inspection. I recommend contacting a pest control company for assistance in removing them. 

Pest Control Pro

6 - Roof Structure & Attic

Descriptions:

The materials, styles and components present and observable are described as follows:

Roof Structure & Attic: Pictures of Attic
Roof Structure & Attic: Decking Material
Plank
Roof Structure & Attic: Unable To Inspect - Safety Hazard

Due there being hypodermic needles just inside the attic access, and there possibly being more in the insulation that are unable to be seen. The attic was not entered fully. 

$
Credit
Comment
6.1.1 - Roof Structure & Attic

Attic Access - Cover is Too Small

The cover for the attic access is too small and it doesn't seal properly. In order to prevent conditioned air from leaking into the attic space, which can lead to energy loss and condensation, I recommend having the cover replaced with a proper fitting one. 

Handyman
$
Credit
Comment
6.1.2 - Roof Structure & Attic

Attic - Bio Hazard

Hypodermic needles were observed just inside the attic access. This is a health and safety hazard. They should be removed and disposed of using proper PPE prior to anyone entering the attic space. 

Qualified Professional

7 - Electrical

Descriptions:

The materials, styles and components present and observable are described as follows:

Service Entrance Conductors: Service Method
Overhead
Service Entrance Conductors: Conductor Material
Unknown
Service Entrance Conductors: Voltage
220 Volt
Service Panel: Picture of Inside Service Panel
Service Panel: Main Panel Location
On the West Exterior Wall
Service Panel: Panel Amperage
125 AMP
Service Panel: Equipment in Panel
Circuit Breaker
Branch Wiring Circuits, Breakers & Fuses: Branch Wiring
Copper
Branch Wiring Circuits, Breakers & Fuses: Type of Sheathing
Non Metallic, Knob & Tube
Fixtures, Fans, Switches & Receptacles: Exterior Light Fixtures Disclaimer

Exterior light fixtures can be on motion detectors, from dusk to dawn sensors, timers, etc. For this reason, we are not always able to confirm whether exterior lights work.

Service Panel: Unable to inspect - Due to Obstructions

The main electrical panel could not be inspected due to obstacles preventing a safe workspace around the panel.

I. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. the service head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter and base; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protection devices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter (AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles and circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled; and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in the integrity of the serviceentrance conductors insulation, drip loop, and vertical clearances from grade and roofs; B. any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcing or excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence of smoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overload devices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security, fire or alarms systems or components, or other warning or signaling systems. G. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground. L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N. inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q. inspect exterior lighting.

$
Credit
Comment
7.2.1 - Service Panel

Deadfront Cover - Missing

The dead front cover for the electrical panel is missing. In order to prevent electrical shock and to keep out unwanted pests and debris, I recommend having a dead front cover installed NS the electrical system evaluated by a licensed electrician. 

Electrical Contractor
$
Credit
Comment
7.4.1 - Fixtures, Fans, Switches & Receptacles

Receptacle - Limited Access

The receptacles were difficult/impossible to access due to the occupants belongings. I recommend having the electrical system evaluated by a licensed electrician to ensure the system is safe. 

Electrical Contractor
$
Credit
Comment
7.4.2 - Fixtures, Fans, Switches & Receptacles

Receptacle - Loose
Living Room

The receptacle(s) was not tightly secured to the box. The receptacle is loose with exposed wiring. I recommend having the receptacle properly secured by a qualified contractor.

Electrical Contractor
$
Credit
Comment
7.5.1 - GFCI & AFCI

GFCI Protection Not Installed

The receptacle(s) were not GFCI protected. In order to protect against electrical shock, I recommend having all receptacles in the garage, on the exterior, and near any water sources such as bathrooms and kitchens protected by GFCI receptacles. For safety reasons, I recommend having  GFCI protection installed. 

Electrical Contractor
$
Credit
Comment
7.6.1 - Smoke & Carbon Monoxide Alarms

CO Alarm - None

No CO alarms were observed in the home. I recommend having a CO alarm installed on each level of the home and within 15 feet of each sleeping room.

Qualified Professional
$
Credit
Comment
7.6.2 - Smoke & Carbon Monoxide Alarms

Smoke Alarm - None

There were no visible smoke alarms in the home. I recommend having proper smoke alarms within 15 feet of all sleeping rooms, and one on each floor of the home.

Qualified Professional

8 - Plumbing

Descriptions:

The materials, styles and components present and observable are described as follows:

Source of Water Supply
Public
Drain, Waste, & Vent Systems: Material
Iron, ABS
Water Supply: Water Supply Material
Galvanized
Water Supply: Distribution Material
Copper
Atmospheric Water Heater: Water Heater

The water heater(s) was visually inspected in order to ensure proper installation and that no leaks, rust, or corrosion were present. The temperature of the water was also checked to ensure the water heater was functioning properly. The American Society of Sanitary Engineering recommends setting the temperature of home water heaters to 135 degrees to 140 degrees Fahrenheit, a range shown to destroy bacteria such as Legionella. At those temperatures, bacteria can neither thrive or survive to contaminate fixtures downstream from the heater. Adjusting a water heater to a higher temperature must always be accompanied by the installation of anti-scald devices in the home by a licensed plumber to prevent potential burn injuries.

Any defects are noted below.

Here is a nice maintenance guide from Lowe's to help.

Atmospheric Water Heater: Manufacturer
Rheem
Atmospheric Water Heater: Location
Exterior Closet
Atmospheric Water Heater: Capacity
40 Gallon
Atmospheric Water Heater: Approximate Age
6 Years Old
Atmospheric Water Heater: Power Source/Type
Gas
Sprinkler System : Sprinkler System - Not Tested or Inspected

The sprinkler system is outside the scope of a home inspection, therefore it was not tested or inspected. Any observations noted are a simply a courtesy.

I. The inspector shall inspect: A. the main water supply shut-off valve; B. the main fuel supply shut-off valve; C. the water heating equipment, including the energy source, venting connections, temperature/pressure-relief (TPR) valves, Watts 210 valves, and seismic bracing; D. interior water supply, including all fixtures and faucets, by running the water; E. all toilets for proper operation by flushing; F. all sinks, tubs and showers for functional drainage; G. the drain, waste and vent system; and H. drainage sump pumps with accessible floats. II. The inspector shall describe: A. whether the water supply is public or private based upon observed evidence; B. the location of the main water supply shut-off valve; C. the location of the main fuel supply shut-off valve; D. the location of any observed fuel-storage system; and E. the capacity of the water heating equipment, if labeled. III. The inspector shall report as in need of correction: A. deficiencies in the water supply by viewing the functional flow in two fixtures operated simultaneously; B. deficiencies in the installation of hot and cold water faucets; C. mechanical drain stops that were missing or did not operate if installed in sinks, lavatories and tubs; and D. toilets that were damaged, had loose connections to the floor, were leaking, or had tank components that did not operate. IV. The inspector is not required to: A. light or ignite pilot flames. B. measure the capacity, temperature, age, life expectancy or adequacy of the water heater. C. inspect the interior of flues or chimneys, combustion air systems, water softener or filtering systems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinkler systems, or fire sprinkler systems. D. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. E. determine the water quality, potability or reliability of the water supply or source. F. open sealed plumbing access panels. G. inspect clothes washing machines or their connections. H. operate any valve. I. test shower pans, tub and shower surrounds or enclosures for leakage or functional overflow protection. J. evaluate the compliance with conservation, energy or building standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. K. determine the effectiveness of anti-siphon, backflow prevention or drain-stop devices. L. determine whether there are sufficient cleanouts for effective cleaning of drains. M. evaluate fuel storage tanks or supply systems. N. inspect wastewater treatment systems. O. inspect water treatment systems or water filters. P. inspect water storage tanks, pressure pumps, or bladder tanks. Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. R. evaluate or determine the adequacy of combustion air. S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-relief valves, control valves, or check valves. T. examine ancillary or auxiliary systems or components, such as, but not limited to, those related to solar water heating and hot water circulation. U. determine the existence or condition of polybutylene plumbing. V. inspect or test for gas or fuel leaks, or indications thereof.

$
Credit
Comment
8.1.1 - Drain, Waste, & Vent Systems

Plumbing Vent - Capped

A plumbing vent on the roof was capped. I recommend asking the seller about the reason why it’s capped. It may be necessary to have a licensed plumber ensure that the DWV system is getting enough ventilation without this vent. 

Inquire With Seller
$
Credit
Comment
8.4.1 - Atmospheric Water Heater

TPR Valve Discharge Pipe - Missing

The water heater temperature and pressure relief valve (TPR valve) does not have a discharge pipe installed. In order to prevent hot water that may be discharged from the end of the pipe from injuring an occupant that's nearby, a discharge pipe is required. I recommend having a discharge pipe installed by a licensed plumber. 

Plumbing Contractor
$
Credit
Comment
8.4.2 - Atmospheric Water Heater

Vent - Insufficient Height Above Roof

The water heater's vent pipe may not be exhausting high enough above the roof. In order for the water heater gases to draft properly, the flue should be of a minimum height, which it doesn’t appear to be. I recommend having this evaluated and addressed as necessary by a licensed plumber or HVAC contractor. 

Plumbing Contractor
$
Credit
Comment
8.6.1 - Sprinkler System

Active Leak

The sprinkler system was leaking. This can lead to high water utility costs. I recommend having this evaluated and addressed as necessary. 

Landscaping Contractor

9 - Heating

Furnace - Unable To Locate

The furnace was unable to be located using the inspection. It’s possible it is located in one of the inaccessible rooms. I recommend asking the seller about the location, operation and age of the furnace. 

I. The inspector shall inspect: A. the heating system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the heating system; B. the energy source; and C. the heating method. III. The inspector shall report as in need of correction: A. any heating system that did not operate; and B. if the heating system was deemed inaccessible. IV. The inspector is not required to: A. inspect or evaluate the interior of flues or chimneys, fire chambers, heat exchangers, combustion air systems, fresh-air intakes, humidifiers, dehumidifiers, electronic air filters, geothermal systems, or solar heating systems. B. inspect fuel tanks or underground or concealed fuel supply systems. C. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. D. light or ignite pilot flames. E. activate heating, heat pump systems, or other heating systems when ambient temperatures or other circumstances are not conducive to safe operation or may damage the equipment. F. override electronic thermostats. G. evaluate fuel quality. H. verify thermostat calibration, heat anticipation, or automatic setbacks, timers, programs or clocks.

10 - Cooling

Evaporative Cooler: Photos of Equipment

I. The inspector shall inspect: A. the cooling system, using normal operating controls. II. The inspector shall describe: A. the location of the thermostat for the cooling system; and B. the cooling method. III. The inspector shall report as in need of correction: A. any cooling system that did not operate; and B. if the cooling system was deemed inaccessible. IV. The inspector is not required to: A. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. B. inspect portable window units, through-wall units, or electronic air filters. C. operate equipment or systems if the exterior temperature is below 65 Fahrenheit, or when other circumstances are not conducive to safe operation or may damage the equipment. D. inspect or determine thermostat calibration, cooling anticipation, or automatic setbacks or clocks. E. examine electrical current, coolant fluids or gases, or coolant leakage.

$
Credit
Comment
10.1.1 - Evaporative Cooler

Evaperative Cooler - Inoperable

Per the tenant, the evaporative cooler is inoperable and has not been used for some time. 

Qualified Professional

11 - Insulation & Ventilation

Descriptions:

The materials, styles and components present and observable are described as follows:

Crawlspace / Basement Wall Insulation: Insulation Type
None
Flooring Insulation: Insulation Type
None
Attic Insulation: Insulation Type
Unknown
Attic Insulation: Average Depth of Insulation
Unobservable
Ventilation & Exhaust : Ventilation Type
Gable Vents
Ventilation & Exhaust : Bathroom Ventilation
Window
Attic Insulation: No Attic Access

Access to the attic was not possible, therefore the insulation was not inspected.

I. The inspector shall inspect: A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas; B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and C. mechanical exhaust systems in the kitchen, bathrooms and laundry area. II. The inspector shall describe: A. the type of insulation observed; and B. the approximate average depth of insulation observed at the unfinished attic floor area or roof structure. III. The inspector shall report as in need of correction: A. the general absence of insulation or ventilation in unfinished spaces. IV. The inspector is not required to: A. enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or, in the inspector's opinion, pose a safety hazard. B. move, touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surface finish or weather seal on or around access panels or covers. E. identify the composition or R-value of insulation material. F. activate thermostatically operated fans. G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.

12 - Foundation & Structure

Descriptions:

The materials, styles and components present and observable are described as follows:

Foundation: Style
Crawlspace
Foundation: Material
Concrete
Foundation: Location of Crawl Space Entrance
West Exterior
Access Door
Floor Structure: Joist/Support Material
Wood Joists
Floor Structure: Post Material
Wood Post
Floor Structure: Sub-floor
Plywood
Floor Structure: Basement/Crawlspace Floor
Dirt, Plastic Sheeting
Crawlspace - Limited Access Due To Electrical Wires

Not all areas of the crawlspace were able to be observed due to multiple wires hanging down and on the crawlspace floor, making it potentially dangerous. 

I. The inspector shall inspect: A. the foundation; B. the basement; C. the crawlspace; and D. structural components. II. The inspector shall describe: A. the type of foundation; and B. the location of the access to the under-floor space. III. The inspector shall report as in need of correction: A. observed indications of wood in contact with or near soil; B. observed indications of active water penetration; C. observed indications of possible foundation movement, such as sheetrock cracks, brick cracks, out-of-square door frames, and unlevel floors; and D. any observed cutting, notching and boring of framing members that may, in the inspector's opinion, present a structural or safety concern. IV. The inspector is not required to: A. enter any crawlspace that is not readily accessible, or where entry could cause damage or pose a hazard to him/herself. B. move stored items or debris. C. operate sump pumps with inaccessible floats. D. identify the size, spacing, span or location or determine the adequacy of foundation bolting, bracing, joists, joist spans or support systems. E. provide any engineering or architectural service. F. report on the adequacy of any structural system or component.

$
Credit
Comment
12.1.1 - Foundation

Moisture Present
Crawlspace

Moisture was observed in the crawl space. No active plumbing leaks were observed, however the moisture is directly adjacent to a sprinkler valve on the other side of the crawlspace wall. I recommend having this evaluated and addressed as necessary. 

Qualified Professional